Timer Close Module TCM
The Timer Close Module provides an automatic door-closing feature that is easily installed and automatically recognized by the operator system. The timer can be selected to start when the door is opened from inputs such as the open button on the wall control, optional radio control input, or auxiliary open input via an optional device. The module is installed in the operator’s electronic box and connects to the main circuit board through an expansion port connector.
Timer Close Module TCM Features
The Timer Close Module is available for the following commercial door operators: RHX®, RSX®, RMZ™, and CDX®
Features
- User-selectable time delay
- Timer hold input
- Auxiliary open input
- Auxiliary reversing inputs
- A sensing device must be used with this module
Specifications
Timer
The timer is selectable from 1 second to 5 minutes. It requires the use of one of the following monitored reversing inputs: Safe–T–Beam® photo eyes or 2-wire monitored edge.
Output Definitions / Ratings: Impending operation warning – Relay contacts to close 2 to 10 seconds before door closing.
- 1 set of Single Pole Single Throw (SPST) normally open contacts
- Rated 3 amps at 120VAC max
Input Definitions:
Timer Hold –This input causes an active timer to reset and hold. The countdown will restart when this input is removed. (This is a class 2 circuit)
- To start a timer hold, Connect this input to the ground (GND) via an optional device.
- To remove a timer hold, Disconnect this input from ground (GND) via an optional device
- In addition to the timer hold input, any active reversing device will reset and hold the timer
Auxiliary Open Input
This input causes a closed or stopped door to open, prevents an open door from closing, and reverses a closing door. This input can be selected to initiate the timer. (This is a Class 2 circuit)
- To start an auxiliary open: Momentarily connect this input to ground (GND) via an optional device.
Normally Closed Reversing Input
This input will reverse a closing door or prevent an open door from closing. This option is selected from a menu on the commercial operator control board.
- To initiate a normally closed reverse: Momentarily disconnect this input from the ground (GND) via a normally closed reversing device.
Monitored Edge Sensor Input
This input will reverse a closing door or prevent an open door from closing. Requires the use of a 2-wire Miller Edge Sensor System designed to work with the commercial operator control board. This option is selected from a menu on the control board.
- To initiate a monitored edge sensor reverse: Momentarily connect this input to ground (GND).
Note: This input will detect broken or short-circuited wiring to the edge sensor and interpret these as active inputs. (No additional equipment required.)
Power Supply Requirements
Voltage – nominal 24V DC via the expension port.
User interface – one 12 position and one 2 position terminal block.
Max Wire Size – 12 AWG, min wire size 20AWG – stranded wire.
Overhead Door® Commercial Operators
Commercial operators provide an integrated door system with our guarantee of reliable performance when you need it most — every day. Built with convenience in mind, our automatic door operators also make it safer and easier to perform daily job duties so you can improve efficiency and close the door on your competition.
Overhead Door®, automatic door operators, are manufactured to meet the performance requirements of our commercial and industrial doors. They offer precise control of our door system for years of trouble-free operation.
Call us Today at (308) 646-2316
Overhead Door Company of Grand Island
2812 W Old Hwy 30, Grand Island, NE 68803
Call us Today at (308) 646-2316
Or Email us on the Form Below.
Business Hours: Monday – Friday 8 AM–4 PM
Call us Today at (308) 646-2316
Or Send us an Email.
Overhead Door Company of Grand Island™ –
2812 W Old Hwy 30, Grand Island, NE 68803